FLOWMWTERS

OPTIBAR
Regarding the range of the transmitters, Requested range cant be changed later to higher range for example OPTIBAR 3050 with range 0....10 bar cant work wit...
Tue, 14 May, 2019 at 11:20 AM
OPTIBAR DP
Steps to commission OPTIBAR 7060 with pitot tube: If the installation is fine please follow below standing points to set the transmitter Close the ...
Tue, 14 May, 2019 at 11:25 AM
Changing from basic I/O to Basic with two analog outpot
Apart from changing the electronics, you do have some options but all require some additional items. 1. If the PLC/DCS can read HART variables, then you...
Tue, 14 May, 2019 at 11:28 AM